NH3 ÃøÁ¤±â
SP-22N7
¾Ï¸ð´Ï¾Æ°¡½ºÃøÁ¤±â
»óǰ»ó¼¼Á¤º¸
NH3 ÃøÁ¤±â
SP 22N7
´ÜÀϰ¡½º°ËÁö±â
[Specification]
| Model | SP-22N7 |
|---|---|
| Measuring gas | NH3 (¾Ï¸ð´Ï¾Æ) |
| Measuring type | Diffusion Type |
| Measuring method | Electrochemical cell |
| Measuring range | 0~100ppm |
| Sensor life time | > 2 year |
| Response time | < 60sec / 90%scale |
| Accuracy | ¡¾3%/Full scale |
| Resolution | 1ppm |
| Parameter Control | Front 2 switch(calibration, maintenance, alarm setting) |
| Operation mode display | Visual : Digital LCD display, Trouble RedLED Audible : buzzer(90dB @ 10cm)" |
| Measuring value display | LCD Display(3-digit) |
| Alarm display | Visual : alarm & status icon, Trouble RedLED Audible : buzzer" |
| Alarm level set | Programmable within dectection range |
| Data Log | Event Log : 20 Data |
| Mounting type | Belt Clip |
| Program set mode | Alarm value(1,2 alarm) time Set Calibration density setting |
| Operating temperature | -20¡É~50¡É |
| Operating humidity | 5% to 95% RH(Non-condensing) |
| Operating power | CR2 Lithium Battery 3V |
| Battery life time | CR2 Battery(3.0v) : 1.2year, At 8hours use of a day |
| Materianl | PC / TPE |
| LCD size | 27(W)*17.5(H) |
| Dimensions | 54(W) X 91(H) X 32(D) mm |
| Weight | 120g (Including Battery) |
| Approval | Ex ia IIC T4 IP67(KGS, ATEX) |
[Drawing]
[Ư¡]